OpenStudio Results

Model Summary


Information Value Units
Building Name NECB 2011-HighriseApartment-NECB HDD Method-CAN_PQ_Sherbrooke.716100_CWEC.epw created: 2017-06-30 13:16:35 +0000 building_name
Net Site Energy 3,587,317 kBtu
Total Building Area 84,351 ft^2
EUI (Based on Net Site Energy and Total Building Area) 42.53 kBtu/ft^2
OpenStudio Standards Building Type HighriseApartment

Value
Weather File Sherbrooke PQ CAN WYEC2-B-04785 WMO#=716100
Latitude 45.43
Longitude -71.7
Elevation 791 (ft)
Time Zone -5.0
North Axis Angle 0.00
ASHRAE Climate Zone

Maximum Dry Bulb (F) Daily Temperature Range (R) Humidity Value Humidity Type Wind Speed (mph) Wind Direction
SHERBROOKE ANN CLG .4% CONDNS DB=>MWB 83.48 21.06 69.62 Wetbulb [F] 8.28 250.0
SHERBROOKE ANN CLG .4% CONDNS WB=>MDB 80.42 21.06 72.14 Wetbulb [F] 8.28 250.0
SHERBROOKE ANN HTG 99.6% CONDNS DB -18.94 0.0 -18.94 Wetbulb [F] 3.8 90.0

Time Setpoint Not Met Time (hr)
During Heating 0.25
During Cooling 11.5
During Occupied Heating 0.25
During Occupied Cooling 8.25

Tolerance for Time Setpoint Not Met Temperature (F)
Heating 1.8
Cooling 1.8

Annual Overview

One or more tables in Annual Overview section returned false and was skipped.

End Use Consumption (kBtu)
Heating 1,737,254
Cooling 219,183
Interior Lighting 299,122
Exterior Lighting 0
Interior Equipment 468,544
Exterior Equipment 0
Fans 209,449
Pumps 2,891
Heat Rejection 199
Humidification 0
Heat Recovery 104
Water Systems 650,582
Refrigeration 0
Generators 0

Fuel Consumption (kBtu)
Electricity 3,587,317
Natural Gas 0
Additional Fuel 0
District Cooling 0
District Heating 0

End Use Consumption (kWh)
Heating 509,139
Cooling 64,236
Interior Lighting 87,664
Exterior Lighting 0
Interior Equipment 137,317
Exterior Equipment 0
Fans 61,383
Pumps 847
Heat Rejection 58
Humidification 0
Heat Recovery 31
Water Systems 190,667
Refrigeration 0
Generators 0

Monthly Overview


Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total
Heating 95384.72 80905.0 60741.67 35549.17 17891.58 8571.75 5120.11 7420.58 16664.81 31376.11 57939.44 91575.0 509139.94
Cooling 129.6 482.73 1373.64 3120.94 6692.36 12263.17 16209.97 13459.86 7134.33 2995.17 219.8 153.87 64235.45
Interior Lighting 7444.64 6725.47 7454.72 7191.47 7454.72 7211.64 7434.56 7454.72 7201.56 7444.64 7211.64 7434.56 87664.33
Exterior Lighting
Interior Equipment 11662.0 10534.06 11666.97 11279.42 11666.97 11289.33 11657.06 11666.97 11284.39 11662.0 11289.33 11657.06 137315.56
Exterior Equipment
Fans 3335.86 3161.5 3847.44 4393.44 5826.5 7392.08 8660.83 7837.78 5766.61 4475.08 3343.58 3342.06 61382.78
Pumps 34.07 31.64 55.04 65.95 90.03 104.32 109.35 109.26 91.17 74.9 51.37 29.11 846.21
Heat Rejection 0.0 0.08 0.34 2.22 4.49 10.75 16.09 14.56 6.56 2.15 0.26 0.0 57.5
Humidification
Heat Recovery 0.23 0.9 6.94 11.66 8.58 2.43 30.72
Water Systems 17297.61 15992.28 17668.06 16553.11 16487.56 15193.78 14984.89 14733.92 14380.69 15170.61 15489.64 16714.33 190666.47
Refrigeration
Generators
Total 135288.5 117832.76 102807.88 78155.95 66115.11 62043.77 64204.51 62706.23 62532.55 73200.66 95545.07 130905.99 1051338.97

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Heating 300.0712 274.1385 205.8864 123.9034 17.1785 64.8974 121.1135 224.2666 312.5355
Cooling 21.2355 43.7128 42.7949 42.7759 2.9712 0.2818
Interior Lighting 20.7431 20.7431 21.5307 21.5307 37.2956 37.2956 37.2956 37.2956 21.0056 20.7431 21.5307 21.5307
Exterior Lighting
Interior Equipment 28.0187 28.0187 28.4158 28.4158 31.5045 31.5045 31.5045 31.5045 28.0849 28.0187 28.4158 28.4158
Exterior Equipment
Fans 4.1967 4.1967 4.6354 4.6354 12.6149 18.7499 17.5063 18.8303 5.8606 4.6354 4.6354 4.6354
Pumps 0.0172 0.0172 0.0172 0.0172 0.1896 0.0172 0.1896 0.1896 0.1322 0.1896 0.0172 0.0172
Heat Rejection 0.0119 0.0296 0.0289
Humidification
Heat Recovery 0.05 0.05 0.05
Water Systems 45.0242 55.2113 61.7801 60.2894 56.945 56.4278 55.5759 53.9682 60.5085 27.9164 59.9757 60.867
Refrigeration
Generators
Total 398.07 382.33 322.27 238.79 176.98 187.76 184.95 184.64 183.46 202.9 338.84 428.0

Utility Bills/Rates

No Data to Show for Utility Bills/Rates

Envelope


Construction Net Area (ft^2) Surface Count R Value (ft^2*h*R/Btu)
Customized opaque construction {50a3605b-77fd-4528-969e-b628441ecfdc} to conductance of 0.162 8,435 9 35.05
Customized opaque construction {60cb0443-3664-469c-bda3-e25acab7d579} to conductance of 0.21 29,112 140 27.04

Construction Area (ft^2) Surface Count U-Factor (Btu/ft^2*h*R)
Customized Fenestration: cond=0.220 tvis=0.220 tsol=0.232 12,383 140 0.3874

Description Total (%) North (%) East (%) South (%) West (%)
Gross Window-Wall Ratio 29.84 30.0 29.62 30.0 29.19
Gross Window-Wall Ratio (Conditioned) 29.84 30.0 29.62 30.0 29.19
Skylight-Roof Ratio 0.0

Space Type Breakdown


Space Type Name Floor Area (ft^2) Standards Building Type Standards Space Type
Space Function Corr. < 2.4m wide-sch-G 8,359 Space Function Corr. < 2.4m wide-sch-G
Space Function Dwelling Unit(s) 75,042 Space Function Dwelling Unit(s)
Space Function Office - enclosed 950 Space Function Office - enclosed

Space Type Summary


Definition Value Unit Inst. Multiplier
Space Function Corr. < 2.4m wide-sch-G People Definition 0.0009 people/ft^2 1.0
Space Function Corr. < 2.4m wide-sch-G Lights Definition 0.7804 W/ft^2 1.0
Space Function Corr. < 2.4m wide-sch-G Ventilation (outdoor air method Sum) 0.0600 cfm/floor area ft^2

Definition Value Unit Inst. Multiplier
Space Function Dwelling Unit(s) People Definition 0.0016 people/ft^2 1.0
Space Function Dwelling Unit(s) Elec Equip Definition 0.4645 W/ft^2 1.0
Space Function Dwelling Unit(s) Lights Definition 0.4645 W/ft^2 1.0
Space Function Dwelling Unit(s) Ventilation (outdoor air method Sum) 0.0680 cfm/floor area ft^2

Definition Value Unit Inst. Multiplier
Space Function Office - enclosed People Definition 0.0046 people/ft^2 1.0
Space Function Office - enclosed Elec Equip Definition 0.6968 W/ft^2 1.0
Space Function Office - enclosed Lights Definition 1.1055 W/ft^2 1.0
Space Function Office - enclosed Ventilation (outdoor air method Sum) 0.0850 cfm/floor area ft^2

Interior Lighting Summary


Zone Lighting Power Density (W/ft^2) Total Power (W) Schedule Name Scheduled Hours/Week (hr) Actual Load Hours/Week (hr) Return Air Fraction Annual Consumption (kWh)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN SPACE FUNCTION OFFICE - ENCLOSED LIGHTS SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 1.11 1050.15 NECB-A-LIGHTING 56.27 56.27 0.0000 3080.56

Plug Loads Summary


Electricity Annual Value (kWh)
InteriorEquipment:Electricity:Zone:SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 2450.0

Exterior Lighting

No Data to Show for Exterior Lighting

Water Use Equipment


Instance Plant Loop Definition Space Peak Flow Rate (gal/min) Flow Rate Schedule Target Temp Range (F)
F2 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 n1 apartment Service Water Use Def 0.06gal/min F2 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 n2 apartment Service Water Use Def 0.06gal/min F2 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F2 ne apartment Service Water Use Def 0.06gal/min F2 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F2 nw apartment Service Water Use Def 0.06gal/min F2 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 s1 apartment Service Water Use Def 0.06gal/min F2 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 s2 apartment Service Water Use Def 0.06gal/min F2 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 se apartment Service Water Use 0.06gal/min Main Service Water Loop F2 se apartment Service Water Use Def 0.06gal/min F2 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F2 sw apartment Service Water Use Def 0.06gal/min F2 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 n1 apartment Service Water Use Def 0.06gal/min F3 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 n2 apartment Service Water Use Def 0.06gal/min F3 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F3 ne apartment Service Water Use Def 0.06gal/min F3 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F3 nw apartment Service Water Use Def 0.06gal/min F3 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 s1 apartment Service Water Use Def 0.06gal/min F3 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 s2 apartment Service Water Use Def 0.06gal/min F3 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 se apartment Service Water Use 0.06gal/min Main Service Water Loop F3 se apartment Service Water Use Def 0.06gal/min F3 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F3 sw apartment Service Water Use Def 0.06gal/min F3 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 n1 apartment Service Water Use Def 0.06gal/min F4 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 n2 apartment Service Water Use Def 0.06gal/min F4 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F4 ne apartment Service Water Use Def 0.06gal/min F4 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F4 nw apartment Service Water Use Def 0.06gal/min F4 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 s1 apartment Service Water Use Def 0.06gal/min F4 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 s2 apartment Service Water Use Def 0.06gal/min F4 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 se apartment Service Water Use 0.06gal/min Main Service Water Loop F4 se apartment Service Water Use Def 0.06gal/min F4 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F4 sw apartment Service Water Use Def 0.06gal/min F4 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 n1 apartment Service Water Use Def 0.06gal/min F6 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 n2 apartment Service Water Use Def 0.06gal/min F6 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F6 ne apartment Service Water Use Def 0.06gal/min F6 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F6 nw apartment Service Water Use Def 0.06gal/min F6 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 s1 apartment Service Water Use Def 0.06gal/min F6 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 s2 apartment Service Water Use Def 0.06gal/min F6 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 se apartment Service Water Use 0.06gal/min Main Service Water Loop F6 se apartment Service Water Use Def 0.06gal/min F6 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F6 sw apartment Service Water Use Def 0.06gal/min F6 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 n1 apartment Service Water Use Def 0.06gal/min F7 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 n2 apartment Service Water Use Def 0.06gal/min F7 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F7 ne apartment Service Water Use Def 0.06gal/min F7 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F7 nw apartment Service Water Use Def 0.06gal/min F7 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 s1 apartment Service Water Use Def 0.06gal/min F7 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 s2 apartment Service Water Use Def 0.06gal/min F7 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 se apartment Service Water Use 0.06gal/min Main Service Water Loop F7 se apartment Service Water Use Def 0.06gal/min F7 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F7 sw apartment Service Water Use Def 0.06gal/min F7 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 n1 apartment Service Water Use Def 0.06gal/min F8 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 n2 apartment Service Water Use Def 0.06gal/min F8 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F8 ne apartment Service Water Use Def 0.06gal/min F8 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F8 nw apartment Service Water Use Def 0.06gal/min F8 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 s1 apartment Service Water Use Def 0.06gal/min F8 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 s2 apartment Service Water Use Def 0.06gal/min F8 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 se apartment Service Water Use 0.06gal/min Main Service Water Loop F8 se apartment Service Water Use Def 0.06gal/min F8 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F8 sw apartment Service Water Use Def 0.06gal/min F8 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 n1 apartment Service Water Use Def 0.06gal/min F9 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 n2 apartment Service Water Use Def 0.06gal/min F9 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F9 ne apartment Service Water Use Def 0.06gal/min F9 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F9 nw apartment Service Water Use Def 0.06gal/min F9 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 s1 apartment Service Water Use Def 0.06gal/min F9 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 s2 apartment Service Water Use Def 0.06gal/min F9 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 se apartment Service Water Use 0.06gal/min Main Service Water Loop F9 se apartment Service Water Use Def 0.06gal/min F9 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F9 sw apartment Service Water Use Def 0.06gal/min F9 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G n1 apartment Service Water Use 0.06gal/min Main Service Water Loop G n1 apartment Service Water Use Def 0.06gal/min G N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G n2 apartment Service Water Use 0.06gal/min Main Service Water Loop G n2 apartment Service Water Use Def 0.06gal/min G N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G ne apartment Service Water Use 0.06gal/min Main Service Water Loop G ne apartment Service Water Use Def 0.06gal/min G NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G nw apartment Service Water Use 0.06gal/min Main Service Water Loop G nw apartment Service Water Use Def 0.06gal/min G NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G s1 apartment Service Water Use 0.06gal/min Main Service Water Loop G s1 apartment Service Water Use Def 0.06gal/min G S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G s2 apartment Service Water Use 0.06gal/min Main Service Water Loop G s2 apartment Service Water Use Def 0.06gal/min G S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G sw apartment Service Water Use 0.06gal/min Main Service Water Loop G sw apartment Service Water Use Def 0.06gal/min G SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M n1 apartment Service Water Use 0.06gal/min Main Service Water Loop M n1 apartment Service Water Use Def 0.06gal/min M N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M n2 apartment Service Water Use 0.06gal/min Main Service Water Loop M n2 apartment Service Water Use Def 0.06gal/min M N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M ne apartment Service Water Use 0.06gal/min Main Service Water Loop M ne apartment Service Water Use Def 0.06gal/min M NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M nw apartment Service Water Use 0.06gal/min Main Service Water Loop M nw apartment Service Water Use Def 0.06gal/min M NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M s1 apartment Service Water Use 0.06gal/min Main Service Water Loop M s1 apartment Service Water Use Def 0.06gal/min M S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M s2 apartment Service Water Use 0.06gal/min Main Service Water Loop M s2 apartment Service Water Use Def 0.06gal/min M S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M se apartment Service Water Use 0.06gal/min Main Service Water Loop M se apartment Service Water Use Def 0.06gal/min M SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M sw apartment Service Water Use 0.06gal/min Main Service Water Loop M sw apartment Service Water Use Def 0.06gal/min M SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
Office Service Water Use 0.03gal/min Main Service Water Loop Office Service Water Use Def 0.03gal/min Office 0.03 NECB-A-Service Water Heating 140.0 to 140.0
T n1 apartment Service Water Use 0.06gal/min Main Service Water Loop T n1 apartment Service Water Use Def 0.06gal/min T N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T n2 apartment Service Water Use 0.06gal/min Main Service Water Loop T n2 apartment Service Water Use Def 0.06gal/min T N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T ne apartment Service Water Use 0.06gal/min Main Service Water Loop T ne apartment Service Water Use Def 0.06gal/min T NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T nw apartment Service Water Use 0.06gal/min Main Service Water Loop T nw apartment Service Water Use Def 0.06gal/min T NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T s1 apartment Service Water Use 0.06gal/min Main Service Water Loop T s1 apartment Service Water Use Def 0.06gal/min T S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T s2 apartment Service Water Use 0.06gal/min Main Service Water Loop T s2 apartment Service Water Use Def 0.06gal/min T S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T se apartment Service Water Use 0.06gal/min Main Service Water Loop T se apartment Service Water Use Def 0.06gal/min T SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T sw apartment Service Water Use 0.06gal/min Main Service Water Loop T sw apartment Service Water Use Def 0.06gal/min T SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0

HVAC Load Profiles


Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Average Outdoor Air Dry Bulb (F) 14.0 14.5 25.6 39.2 52.4 61.2 64.7 62.1 53.0 43.1 30.4 16.6
Cooling Load (MBtu) 0.44 1.65 4.69 10.65 22.84 41.84 55.31 45.93 24.34 10.22 0.75 0.53
Heating Load (MBtu) 325.47 276.06 207.26 121.3 61.05 29.25 17.47 25.32 56.86 107.06 197.7 312.47

Zone Conditions


Zone Unmet Htg (hr) Unmet Htg - Occ (hr) < 56 (F) 56-61 (F) 61-66 (F) 66-68 (F) 68-70 (F) 70-72 (F) 72-74 (F) 74-76 (F) 76-78 (F) 78-83 (F) 83-88 (F) >= 88 (F) Unmet Clg (hr) Unmet Clg - Occ (hr) Mean Temp (F)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 25 459 2334 1208 4734 0 0 0 0 0 0 73.4 (F)
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 22 277 594 2911 950 4006 0 0 0 0 0 0 72.9 (F)
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 23 275 595 2885 969 4013 0 0 0 0 0 0 72.9 (F)
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 264 390 446 2965 675 4020 0 0 0 0 0 0 72.6 (F)
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 262 400 454 2992 765 3887 0 0 0 0 0 0 72.6 (F)
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 2 84 344 1475 1315 5530 10 0 0 0 3 3 73.7 (F)
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 3 85 344 1467 1304 5547 10 0 0 0 3 3 73.7 (F)
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 141 293 425 1969 1015 4915 2 0 0 0 0 0 73.2 (F)
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 112 298 471 2070 972 4837 0 0 0 0 0 0 73.2 (F)
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 22 423 2255 1236 4824 0 0 0 0 0 0 73.5 (F)
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 23 272 583 2846 926 4110 0 0 0 0 0 0 72.9 (F)
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 24 272 584 2826 919 4135 0 0 0 0 0 0 72.9 (F)
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 269 384 432 2949 650 4076 0 0 0 0 0 0 72.7 (F)
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 267 391 441 2972 746 3943 0 0 0 0 0 0 72.6 (F)
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 2 84 328 1394 1316 5627 9 0 0 0 3 3 73.8 (F)
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 3 82 328 1388 1307 5643 9 0 0 0 3 3 73.8 (F)
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 119 285 427 2008 973 4947 1 0 0 0 0 0 73.2 (F)
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 115 285 455 2044 971 4890 0 0 0 0 0 0 73.2 (F)
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 22 427 2242 1232 4837 0 0 0 0 0 0 73.5 (F)
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 28 281 573 2843 910 4125 0 0 0 0 0 0 72.9 (F)
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 27 283 575 2822 902 4151 0 0 0 0 0 0 72.9 (F)
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 283 380 423 2948 659 4067 0 0 0 0 0 0 72.7 (F)
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 280 390 431 2976 742 3941 0 0 0 0 0 0 72.6 (F)
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 5 88 327 1410 1306 5616 8 0 0 0 2 2 73.8 (F)
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 5 87 326 1403 1299 5631 9 0 0 0 3 3 73.8 (F)
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 128 287 427 2032 957 4928 1 0 0 0 0 0 73.2 (F)
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 124 289 452 2063 951 4881 0 0 0 0 0 0 73.2 (F)
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 28 447 2307 1185 4793 0 0 0 0 0 0 73.4 (F)
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 32 298 580 2887 883 4080 0 0 0 0 0 0 72.9 (F)
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 33 300 575 2869 885 4098 0 0 0 0 0 0 72.9 (F)
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 299 386 416 2984 668 4007 0 0 0 0 0 0 72.6 (F)
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 296 399 423 2995 756 3891 0 0 0 0 0 0 72.6 (F)
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 8 98 339 1475 1309 5524 7 0 0 0 2 2 73.7 (F)
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 8 98 340 1467 1312 5527 8 0 0 0 2 2 73.7 (F)
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 149 298 430 2097 935 4850 1 0 0 0 0 0 73.2 (F)
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 150 295 446 2145 909 4815 0 0 0 0 0 0 73.1 (F)
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 32 458 2393 1114 4763 0 0 0 0 0 0 73.4 (F)
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 38 309 580 2930 873 4030 0 0 0 0 0 0 72.8 (F)
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 39 311 577 2922 875 4036 0 0 0 0 0 0 72.9 (F)
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 313 388 411 3002 682 3964 0 0 0 0 0 0 72.6 (F)
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 304 405 424 3029 742 3856 0 0 0 0 0 0 72.6 (F)
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 11 103 357 1540 1303 5439 7 0 0 0 2 2 73.7 (F)
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 12 103 359 1530 1297 5452 7 0 0 0 2 2 73.7 (F)
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 157 302 436 2150 904 4809 2 0 0 0 0 0 73.1 (F)
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 157 304 450 2202 878 4769 0 0 0 0 0 0 73.1 (F)
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 37 499 2514 1053 4657 0 0 0 0 0 0 73.3 (F)
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 51 328 594 2992 868 3927 0 0 0 0 0 0 72.8 (F)
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 51 330 591 2987 861 3940 0 0 0 0 0 0 72.8 (F)
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 329 407 403 3032 735 3854 0 0 0 0 0 0 72.5 (F)
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 323 404 437 3073 742 3781 0 0 0 0 0 0 72.5 (F)
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 14 120 395 1666 1273 5286 6 0 0 0 2 2 73.6 (F)
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 14 122 394 1657 1276 5290 7 0 0 0 2 2 73.6 (F)
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 179 318 433 2230 869 4728 3 0 0 0 0 0 73.1 (F)
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 177 319 445 2306 838 4675 0 0 0 0 0 0 73.0 (F)
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 85 595 2708 1018 4354 0 0 0 0 0 0 73.2 (F)
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 97 374 598 3162 862 3667 0 0 0 0 0 0 72.6 (F)
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 98 372 598 3146 866 3680 0 0 0 0 0 0 72.6 (F)
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 397 410 404 3118 787 3644 0 0 0 0 0 0 72.4 (F)
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 392 418 435 3178 727 3610 0 0 0 0 0 0 72.4 (F)
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 32 184 473 1945 1211 4909 6 0 0 0 1 1 73.4 (F)
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 32 182 473 1940 1209 4917 7 0 0 0 1 1 73.4 (F)
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 237 343 443 2425 815 4492 5 0 0 0 0 0 72.9 (F)
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 237 355 452 2454 841 4421 0 0 0 0 0 0 72.9 (F)
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN 0 0 0 0 4 165 552 2847 1055 4101 36 0 0 0 4 4 73.2 (F)
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 50 351 613 3042 1036 3668 0 0 0 0 0 0 72.7 (F)
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 50 350 611 3037 1019 3693 0 0 0 0 0 0 72.7 (F)
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 330 426 420 3063 791 3730 0 0 0 0 0 0 72.5 (F)
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 323 434 456 3071 862 3614 0 0 0 0 0 0 72.4 (F)
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 11 151 450 1697 1401 5029 19 2 0 0 4 4 73.5 (F)
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 16 156 450 1683 1411 5022 20 2 0 0 4 4 73.5 (F)
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 182 345 478 2197 1051 4507 0 0 0 0 0 0 73.0 (F)
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 28 436 2265 1211 4820 0 0 0 0 0 0 73.5 (F)
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 32 287 572 2860 903 4106 0 0 0 0 0 0 72.9 (F)
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 32 288 575 2840 894 4131 0 0 0 0 0 0 72.9 (F)
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 291 384 417 2964 664 4040 0 0 0 0 0 0 72.6 (F)
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 286 397 427 2980 746 3924 0 0 0 0 0 0 72.6 (F)
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 7 89 335 1433 1308 5580 8 0 0 0 2 2 73.8 (F)
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 7 89 337 1421 1309 5588 9 0 0 0 2 2 73.8 (F)
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 138 296 424 2063 950 4888 1 0 0 0 0 0 73.2 (F)
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 135 299 444 2110 917 4855 0 0 0 0 0 0 73.2 (F)
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 0 0 0 0 520 638 699 1668 1756 2967 316 188 8 0 5 2 72.5 (F)
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0 0 0 0 540 390 432 3088 991 3319 0 0 0 0 0 0 72.2 (F)
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0 0 0 0 777 373 345 3484 893 2888 0 0 0 0 0 0 71.9 (F)
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0 0 0 0 776 378 334 3478 902 2892 0 0 0 0 0 0 71.9 (F)
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0 0 0 0 938 300 297 3476 791 2958 0 0 0 0 0 0 71.8 (F)
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0 0 0 0 957 303 335 3493 782 2890 0 0 0 0 0 0 71.8 (F)
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 627 387 349 2768 963 3656 10 0 0 0 2 2 72.3 (F)
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 623 387 351 2768 952 3669 10 0 0 0 3 3 72.3 (F)
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 858 276 330 2931 809 3552 4 0 0 0 0 0 72.1 (F)
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 873 291 350 2959 832 3455 0 0 0 0 0 0 72.1 (F)

Zone < 30 (%) 30-35 (%) 35-40 (%) 40-45 (%) 45-50 (%) 50-55 (%) 55-60 (%) 60-65 (%) 65-70 (%) 70-75 (%) 75-80 (%) >= 80 (%) Mean Relative Humidity (%)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 5229 706 613 751 785 441 206 26 3 0 0 0 26.7 (%)
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 3518 976 898 788 742 829 601 303 102 3 0 0 35.5 (%)
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 3517 977 904 790 742 821 607 292 107 3 0 0 35.4 (%)
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 3550 956 926 809 871 865 452 258 70 3 0 0 34.9 (%)
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 3535 972 897 815 912 872 460 235 62 0 0 0 34.9 (%)
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 3799 960 959 745 768 778 480 236 35 0 0 0 33.9 (%)
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 3797 961 960 741 768 778 490 229 36 0 0 0 33.9 (%)
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 3735 917 1004 810 896 788 388 191 31 0 0 0 33.9 (%)
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 3725 918 966 811 917 813 382 199 29 0 0 0 34.0 (%)
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 5251 696 617 754 779 441 204 16 2 0 0 0 26.6 (%)
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 3558 980 911 788 746 804 596 284 91 2 0 0 35.2 (%)
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 3560 977 915 789 740 812 586 292 87 2 0 0 35.2 (%)
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 3591 968 928 809 855 856 444 250 57 2 0 0 34.7 (%)
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 3574 983 884 824 903 858 462 217 55 0 0 0 34.7 (%)
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 3846 972 934 761 758 769 477 217 26 0 0 0 33.7 (%)
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 3844 971 934 759 760 770 478 215 29 0 0 0 33.7 (%)
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 3782 913 985 809 877 790 384 193 27 0 0 0 33.7 (%)
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 3760 921 975 809 905 797 386 184 23 0 0 0 33.8 (%)
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 5258 690 618 753 781 438 204 16 2 0 0 0 26.6 (%)
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 3583 975 906 781 745 805 596 280 87 2 0 0 35.1 (%)
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 3583 973 909 787 739 809 586 285 87 2 0 0 35.1 (%)
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 3611 974 916 802 852 851 447 248 57 2 0 0 34.6 (%)
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 3596 983 885 814 890 853 470 215 54 0 0 0 34.6 (%)
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 3864 971 924 759 757 769 473 218 25 0 0 0 33.6 (%)
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 3864 966 931 753 759 770 474 215 28 0 0 0 33.6 (%)
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 3801 915 974 801 869 792 383 198 27 0 0 0 33.6 (%)
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 3784 928 957 808 892 800 386 183 22 0 0 0 33.7 (%)
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 5253 694 615 752 779 444 205 16 2 0 0 0 26.6 (%)
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 3597 974 895 779 740 809 591 287 86 2 0 0 35.1 (%)
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 3601 969 897 784 734 812 586 288 87 2 0 0 35.1 (%)
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 3636 973 909 786 843 844 464 242 61 2 0 0 34.5 (%)
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 3623 982 878 796 882 852 474 218 55 0 0 0 34.5 (%)
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 3871 977 918 750 757 764 478 218 27 0 0 0 33.6 (%)
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 3872 971 920 748 757 771 473 220 28 0 0 0 33.6 (%)
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 3827 907 965 788 867 785 389 203 29 0 0 0 33.6 (%)
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 3801 927 953 792 887 802 388 183 27 0 0 0 33.6 (%)
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 5244 699 614 752 779 446 207 17 2 0 0 0 26.6 (%)
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 3596 970 892 786 734 807 596 287 90 2 0 0 35.1 (%)
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 3600 963 893 792 730 813 589 288 90 2 0 0 35.1 (%)
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 3646 969 902 782 842 838 467 246 66 2 0 0 34.5 (%)
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 3631 974 874 799 878 849 475 225 55 0 0 0 34.5 (%)
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 3866 972 922 751 757 765 479 217 31 0 0 0 33.6 (%)
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 3866 967 924 749 758 768 478 220 30 0 0 0 33.6 (%)
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 3828 906 965 783 864 787 395 202 30 0 0 0 33.5 (%)
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 3808 923 947 786 888 805 391 185 27 0 0 0 33.6 (%)
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 5223 710 616 755 776 446 213 19 2 0 0 0 26.7 (%)
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 3584 967 886 780 735 825 597 289 95 2 0 0 35.1 (%)
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 3582 965 895 784 729 821 596 290 96 2 0 0 35.1 (%)
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 3643 970 895 782 834 848 467 244 74 3 0 0 34.5 (%)
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 3630 974 867 793 876 858 476 226 60 0 0 0 34.5 (%)
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 3841 972 930 748 761 772 481 223 32 0 0 0 33.7 (%)
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 3838 970 933 749 759 776 477 226 32 0 0 0 33.7 (%)
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 3819 904 968 778 861 792 398 208 32 0 0 0 33.6 (%)
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 3802 921 945 782 894 804 394 188 30 0 0 0 33.6 (%)
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 5171 726 608 771 784 442 226 29 3 0 0 0 26.9 (%)
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 3544 970 849 792 739 847 614 288 113 4 0 0 35.4 (%)
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 3543 974 847 793 734 853 609 289 114 4 0 0 35.4 (%)
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 3622 962 877 786 840 865 468 244 88 8 0 0 34.6 (%)
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 3608 972 844 790 888 861 479 237 78 3 0 0 34.7 (%)
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 3781 945 952 741 777 800 474 242 48 0 0 0 34.0 (%)
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 3781 943 951 740 780 796 476 242 51 0 0 0 34.0 (%)
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 3771 924 949 779 864 794 410 219 49 1 0 0 33.8 (%)
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 3756 929 931 779 901 823 393 206 41 1 0 0 33.8 (%)
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN 3190 838 906 2854 617 152 97 56 31 11 6 2 33.8 (%)
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 3392 974 876 799 688 809 674 364 152 30 2 0 36.3 (%)
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 3396 971 888 786 698 800 673 364 152 30 2 0 36.3 (%)
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 3442 934 902 813 856 787 572 291 140 21 2 0 35.8 (%)
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 3417 958 870 819 869 809 592 279 131 16 0 0 35.8 (%)
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 3645 959 932 725 734 782 548 320 106 9 0 0 34.8 (%)
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 3648 952 936 726 740 771 549 323 103 12 0 0 34.9 (%)
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 3568 941 952 791 861 846 434 276 82 9 0 0 34.8 (%)
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 5256 692 617 754 775 443 205 16 2 0 0 0 26.6 (%)
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 3591 976 898 781 742 805 594 285 86 2 0 0 35.1 (%)
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 3595 971 904 782 736 812 585 287 86 2 0 0 35.1 (%)
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 3626 974 910 797 845 848 454 246 58 2 0 0 34.5 (%)
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 3612 985 879 805 886 850 472 216 55 0 0 0 34.5 (%)
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 3866 978 920 753 757 767 475 219 25 0 0 0 33.6 (%)
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 3870 969 923 753 757 769 474 217 28 0 0 0 33.6 (%)
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 3816 909 969 795 869 789 386 199 28 0 0 0 33.6 (%)
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 3793 928 954 802 886 803 385 184 25 0 0 0 33.6 (%)
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 3733 873 991 1768 1346 49 0 0 0 0 0 0 31.9 (%)
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 5032 739 535 751 695 542 306 115 41 4 0 0 27.6 (%)
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 3747 900 820 685 748 695 617 363 142 40 3 0 34.5 (%)
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 3750 896 826 690 736 700 610 362 144 43 3 0 34.5 (%)
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 3832 829 816 738 748 663 606 334 147 43 4 0 34.2 (%)
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 3818 830 815 705 778 714 596 321 137 43 3 0 34.2 (%)
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 3850 895 829 685 715 657 619 350 124 35 1 0 34.0 (%)
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 3851 894 819 690 716 651 622 356 125 35 1 0 34.0 (%)
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 3891 846 837 753 755 633 583 292 134 33 3 0 33.7 (%)
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 3873 843 855 738 753 704 554 279 127 31 3 0 33.7 (%)

Zone Overview


Area (ft^2) Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume (ft^3) Multiplier Above Ground Gross Wall Area (ft^2) Underground Gross Wall Area (ft^2) Window Glass Area (ft^2) Lighting (W/ft^2) People (ft^2/person) Plug and Process (W/ft^2)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 48.11 0.78 1075.31 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 1.11 215.06 0.7
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
Total 84351.17 843456.88 41495.09 0.0 12382.7 0.5 656.38 0.42
Conditioned Total 84351.17 843456.88 41495.09 0.0 12382.7 0.5 656.38 0.42
Unconditioned Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Not Part of Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Heating/Cooling Calculated Design Load Design Load With Sizing Factor Calculated Design Air Flow (ft^3/min) Design Air Flow With Sizing Factor (ft^3/min) Date/Time Of Peak Outdoor Temperature at Peak Load (F) Outdoor Humidity Ratio at Peak Load (lbWater/lbAir)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN Cooling 0.32 (ton) 0.35 (ton) 180.1 199.17 7/21 20:00:00 72.95 0.01
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN Heating 5.67 (kBtu/h) 7.37 (kBtu/h) 137.73 177.99 1/21 09:00:00 -18.94 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.27 (ton) 0.3 (ton) 154.68 171.63 7/21 20:00:00 72.95 0.01
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 5.48 (kBtu/h) 7.13 (kBtu/h) 135.61 175.87 1/21 09:30:00 -18.94 0.0
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.27 (ton) 0.3 (ton) 152.56 167.39 7/21 20:00:00 72.95 0.01
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 5.48 (kBtu/h) 7.13 (kBtu/h) 135.61 175.87 1/21 09:30:00 -18.94 0.0
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.54 (ton) 0.6 (ton) 307.24 339.02 7/21 09:00:00 71.89 0.01
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 8.3 (kBtu/h) 10.79 (kBtu/h) 205.53 266.98 1/21 09:30:00 -18.94 0.0
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.59 (ton) 0.65 (ton) 334.78 366.57 7/21 17:00:00 80.53 0.01
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 8.25 (kBtu/h) 10.72 (kBtu/h) 203.41 264.86 1/21 09:30:00 -18.94 0.0
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.37 (ton) 0.41 (ton) 211.89 233.08 7/21 13:15:00 82.69 0.01
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 5.48 (kBtu/h) 7.13 (kBtu/h) 135.61 175.87 1/21 09:30:00 -18.94 0.0
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.38 (ton) 0.42 (ton) 216.13 237.31 7/21 13:15:00 82.69 0.01
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 5.49 (kBtu/h) 7.14 (kBtu/h) 135.61 175.87 1/21 09:30:00 -18.94 0.0
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.59 (ton) 0.65 (ton) 336.9 370.8 7/21 09:00:00 71.89 0.01
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 8.34 (kBtu/h) 10.84 (kBtu/h) 205.53 269.1 1/21 09:30:00 -18.94 0.0
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.68 (ton) 0.75 (ton) 383.52 421.66 7/21 17:00:00 80.53 0.01
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 8.25 (kBtu/h) 10.72 (kBtu/h) 203.41 264.86 1/21 09:30:00 -18.94 0.0
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN Cooling 0.32 (ton) 0.35 (ton) 180.1 199.17 7/21 20:00:00 72.95 0.01
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN Heating 5.57 (kBtu/h) 7.24 (kBtu/h) 135.61 175.87 1/21 09:00:00 -18.94 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.31 (ton) 158.92 173.75 7/21 20:00:00 72.95 0.01
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 5.5 (kBtu/h) 7.15 (kBtu/h) 135.61 177.99 1/21 09:30:00 -18.94 0.0
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.27 (ton) 0.3 (ton) 154.68 171.63 7/21 20:00:00 72.95 0.01
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 5.51 (kBtu/h) 7.16 (kBtu/h) 135.61 177.99 1/21 09:30:00 -18.94 0.0
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.55 (ton) 0.6 (ton) 311.48 341.14 7/21 09:00:00 71.89 0.01
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 8.36 (kBtu/h) 10.87 (kBtu/h) 207.65 269.1 1/21 09:30:00 -18.94 0.0
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.59 (ton) 0.65 (ton) 336.9 370.8 7/21 17:00:00 80.53 0.01
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 8.31 (kBtu/h) 10.81 (kBtu/h) 205.53 266.98 1/21 09:30:00 -18.94 0.0
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.38 (ton) 0.42 (ton) 216.13 237.31 7/21 13:15:00 82.69 0.01
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 5.5 (kBtu/h) 7.15 (kBtu/h) 135.61 177.99 1/21 09:30:00 -18.94 0.0
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.38 (ton) 0.42 (ton) 218.24 239.43 7/21 13:15:00 82.69 0.01
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 5.51 (kBtu/h) 7.16 (kBtu/h) 135.61 177.99 1/21 09:30:00 -18.94 0.0
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.58 (ton) 0.64 (ton) 330.55 362.33 7/21 09:00:00 71.89 0.01
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 8.37 (kBtu/h) 10.89 (kBtu/h) 207.65 269.1 1/21 09:30:00 -18.94 0.0
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.68 (ton) 0.75 (ton) 385.64 425.89 7/21 17:00:00 80.53 0.01
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 8.31 (kBtu/h) 10.81 (kBtu/h) 205.53 266.98 1/21 09:30:00 -18.94 0.0
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN Cooling 0.32 (ton) 0.35 (ton) 180.1 199.17 7/21 20:00:00 72.95 0.01
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN Heating 5.59 (kBtu/h) 7.27 (kBtu/h) 135.61 175.87 1/21 09:00:00 -18.94 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.31 (ton) 158.92 175.87 7/21 20:00:00 72.95 0.01
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 5.56 (kBtu/h) 7.22 (kBtu/h) 137.73 177.99 1/21 09:30:00 -18.94 0.0
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.3 (ton) 156.8 171.63 7/21 20:00:00 72.95 0.01
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 5.56 (kBtu/h) 7.23 (kBtu/h) 137.73 180.1 1/21 09:30:00 -18.94 0.0
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.55 (ton) 0.6 (ton) 311.48 341.14 7/21 09:00:00 71.89 0.01
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 8.44 (kBtu/h) 10.98 (kBtu/h) 209.77 271.22 1/21 09:30:00 -18.94 0.0
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.65 (ton) 336.9 370.8 7/21 17:00:00 80.53 0.01
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 8.39 (kBtu/h) 10.91 (kBtu/h) 207.65 271.22 1/21 09:30:00 -18.94 0.0
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.38 (ton) 0.42 (ton) 216.13 237.31 7/21 13:15:00 82.69 0.01
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 5.56 (kBtu/h) 7.22 (kBtu/h) 137.73 177.99 1/21 09:30:00 -18.94 0.0
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.39 (ton) 0.42 (ton) 218.24 241.55 7/21 13:15:00 82.69 0.01
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 5.56 (kBtu/h) 7.23 (kBtu/h) 137.73 180.1 1/21 09:30:00 -18.94 0.0
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.58 (ton) 0.64 (ton) 328.43 362.33 7/21 09:00:00 71.89 0.01
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 8.44 (kBtu/h) 10.98 (kBtu/h) 209.77 271.22 1/21 09:30:00 -18.94 0.0
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.68 (ton) 0.75 (ton) 387.76 425.89 7/21 16:45:00 80.96 0.01
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 8.39 (kBtu/h) 10.91 (kBtu/h) 207.65 271.22 1/21 09:30:00 -18.94 0.0
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN Cooling 0.32 (ton) 0.35 (ton) 180.1 199.17 7/21 20:00:00 72.95 0.01
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN Heating 5.65 (kBtu/h) 7.34 (kBtu/h) 137.73 177.99 1/21 09:00:00 -18.94 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.31 (ton) 158.92 173.75 7/21 20:00:00 72.95 0.01
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 5.65 (kBtu/h) 7.35 (kBtu/h) 139.85 182.22 1/21 09:30:00 -18.94 0.0
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.27 (ton) 0.3 (ton) 156.8 171.63 7/21 20:00:00 72.95 0.01
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 5.65 (kBtu/h) 7.35 (kBtu/h) 139.85 182.22 1/21 09:30:00 -18.94 0.0
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.55 (ton) 0.6 (ton) 309.36 341.14 7/21 09:00:00 71.89 0.01
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 8.57 (kBtu/h) 11.15 (kBtu/h) 211.89 275.45 1/21 09:30:00 -18.94 0.0
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 336.9 370.8 7/21 17:00:00 80.53 0.01
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 8.52 (kBtu/h) 11.08 (kBtu/h) 211.89 275.45 1/21 09:30:00 -18.94 0.0
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.38 (ton) 0.42 (ton) 216.13 237.31 7/21 13:15:00 82.69 0.01
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 5.65 (kBtu/h) 7.35 (kBtu/h) 139.85 182.22 1/21 09:30:00 -18.94 0.0
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.39 (ton) 0.43 (ton) 218.24 241.55 7/21 13:15:00 82.69 0.01
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 5.65 (kBtu/h) 7.35 (kBtu/h) 139.85 182.22 1/21 09:30:00 -18.94 0.0
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.58 (ton) 0.63 (ton) 328.43 360.21 7/21 09:00:00 71.89 0.01
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 8.57 (kBtu/h) 11.15 (kBtu/h) 211.89 275.45 1/21 09:30:00 -18.94 0.0
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.68 (ton) 0.75 (ton) 387.76 425.89 7/21 16:45:00 80.96 0.01
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 8.52 (kBtu/h) 11.08 (kBtu/h) 211.89 275.45 1/21 09:30:00 -18.94 0.0
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN Cooling 0.32 (ton) 0.35 (ton) 180.1 199.17 7/21 20:00:00 72.95 0.01
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN Heating 5.69 (kBtu/h) 7.39 (kBtu/h) 137.73 180.1 1/21 09:00:00 -18.94 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.31 (ton) 158.92 173.75 7/21 20:00:00 72.95 0.01
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 5.7 (kBtu/h) 7.41 (kBtu/h) 141.96 184.34 1/21 09:30:00 -18.94 0.0
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.27 (ton) 0.3 (ton) 156.8 171.63 7/21 20:00:00 72.95 0.01
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 5.71 (kBtu/h) 7.42 (kBtu/h) 141.96 184.34 1/21 09:30:00 -18.94 0.0
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.55 (ton) 0.6 (ton) 309.36 341.14 7/21 09:00:00 71.89 0.01
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 8.64 (kBtu/h) 11.23 (kBtu/h) 214.01 277.57 1/21 09:30:00 -18.94 0.0
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 336.9 370.8 7/21 17:00:00 80.53 0.01
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 8.58 (kBtu/h) 11.16 (kBtu/h) 211.89 275.45 1/21 09:30:00 -18.94 0.0
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.38 (ton) 0.42 (ton) 216.13 237.31 7/21 13:15:00 82.69 0.01
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 5.7 (kBtu/h) 7.41 (kBtu/h) 141.96 184.34 1/21 09:30:00 -18.94 0.0
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.39 (ton) 0.43 (ton) 218.24 241.55 7/21 13:15:00 82.69 0.01
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 5.71 (kBtu/h) 7.42 (kBtu/h) 141.96 184.34 1/21 09:30:00 -18.94 0.0
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.58 (ton) 0.63 (ton) 326.31 360.21 7/21 09:00:00 71.89 0.01
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 8.64 (kBtu/h) 11.23 (kBtu/h) 214.01 277.57 1/21 09:30:00 -18.94 0.0
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.68 (ton) 0.75 (ton) 387.76 425.89 7/21 16:45:00 80.96 0.01
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 8.58 (kBtu/h) 11.16 (kBtu/h) 211.89 275.45 1/21 09:30:00 -18.94 0.0
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN Cooling 0.32 (ton) 0.35 (ton) 180.1 199.17 7/21 20:00:00 72.95 0.01
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN Heating 5.82 (kBtu/h) 7.56 (kBtu/h) 141.96 184.34 1/21 09:00:00 -18.94 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.31 (ton) 158.92 175.87 7/21 20:00:00 72.95 0.01
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 5.82 (kBtu/h) 7.57 (kBtu/h) 144.08 188.58 1/21 09:30:00 -18.94 0.0
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.3 (ton) 156.8 171.63 7/21 20:00:00 72.95 0.01
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 5.83 (kBtu/h) 7.57 (kBtu/h) 144.08 188.58 1/21 09:30:00 -18.94 0.0
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.54 (ton) 0.6 (ton) 309.36 339.02 7/21 09:00:00 71.89 0.01
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 8.77 (kBtu/h) 11.4 (kBtu/h) 218.24 281.81 1/21 09:30:00 -18.94 0.0
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 339.02 370.8 7/21 17:00:00 80.53 0.01
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 8.71 (kBtu/h) 11.32 (kBtu/h) 216.13 279.69 1/21 09:30:00 -18.94 0.0
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.38 (ton) 0.42 (ton) 216.13 237.31 7/21 13:15:00 82.69 0.01
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 5.82 (kBtu/h) 7.57 (kBtu/h) 144.08 188.58 1/21 09:30:00 -18.94 0.0
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.39 (ton) 0.42 (ton) 218.24 241.55 7/21 13:15:00 82.69 0.01
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 5.83 (kBtu/h) 7.57 (kBtu/h) 144.08 188.58 1/21 09:30:00 -18.94 0.0
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.57 (ton) 0.63 (ton) 326.31 358.09 7/21 09:00:00 71.89 0.01
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 8.77 (kBtu/h) 11.4 (kBtu/h) 218.24 281.81 1/21 09:30:00 -18.94 0.0
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.68 (ton) 0.75 (ton) 387.76 425.89 7/21 16:45:00 80.96 0.01
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 8.71 (kBtu/h) 11.32 (kBtu/h) 216.13 279.69 1/21 09:30:00 -18.94 0.0
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN Cooling 0.33 (ton) 0.36 (ton) 186.46 203.41 7/21 20:00:00 72.95 0.01
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN Heating 6.66 (kBtu/h) 8.66 (kBtu/h) 161.03 209.77 1/21 09:00:00 -18.94 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 165.27 180.1 7/21 20:00:00 72.95 0.01
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 6.45 (kBtu/h) 8.39 (kBtu/h) 158.92 207.65 1/21 09:30:00 -18.94 0.0
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.31 (ton) 161.03 177.99 7/21 20:00:00 72.95 0.01
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 6.46 (kBtu/h) 8.39 (kBtu/h) 161.03 207.65 1/21 09:30:00 -18.94 0.0
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.54 (ton) 0.6 (ton) 307.24 336.9 7/21 09:00:00 71.89 0.01
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 9.39 (kBtu/h) 12.21 (kBtu/h) 233.08 303.0 1/21 09:30:00 -18.94 0.0
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.61 (ton) 0.67 (ton) 347.5 381.4 7/21 17:00:00 80.53 0.01
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 9.33 (kBtu/h) 12.13 (kBtu/h) 230.96 300.88 1/21 09:30:00 -18.94 0.0
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.39 (ton) 0.43 (ton) 220.36 243.67 7/21 13:15:00 82.69 0.01
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 6.45 (kBtu/h) 8.39 (kBtu/h) 158.92 207.65 1/21 09:30:00 -18.94 0.0
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.39 (ton) 0.43 (ton) 224.6 245.79 7/21 13:15:00 82.69 0.01
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 6.46 (kBtu/h) 8.39 (kBtu/h) 161.03 207.65 1/21 09:30:00 -18.94 0.0
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.57 (ton) 0.63 (ton) 324.19 355.97 7/21 13:00:00 82.44 0.01
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 9.39 (kBtu/h) 12.21 (kBtu/h) 233.08 303.0 1/21 09:30:00 -18.94 0.0
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.7 (ton) 0.77 (ton) 396.23 436.49 7/21 17:00:00 80.53 0.01
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 9.33 (kBtu/h) 12.13 (kBtu/h) 230.96 300.88 1/21 09:30:00 -18.94 0.0
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN Cooling 0.37 (ton) 0.41 (ton) 209.77 230.96 7/21 09:00:00 71.89 0.01
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN Heating 6.32 (kBtu/h) 8.21 (kBtu/h) 152.56 199.17 1/21 09:00:00 -18.94 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.24 (ton) 0.26 (ton) 135.61 148.32 7/21 20:00:00 72.95 0.01
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 5.4 (kBtu/h) 7.02 (kBtu/h) 133.49 173.75 1/21 09:30:00 -18.94 0.0
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.23 (ton) 0.26 (ton) 131.37 144.08 7/21 20:00:00 72.95 0.01
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 5.4 (kBtu/h) 7.03 (kBtu/h) 133.49 173.75 1/21 09:30:00 -18.94 0.0
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.58 (ton) 0.63 (ton) 326.31 360.21 7/21 09:00:00 71.89 0.01
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 8.05 (kBtu/h) 10.46 (kBtu/h) 194.94 254.27 1/21 09:00:00 -18.94 0.0
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 343.26 377.16 7/21 17:00:00 80.53 0.01
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 8.0 (kBtu/h) 10.41 (kBtu/h) 194.94 252.15 1/21 09:00:00 -18.94 0.0
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.38 (ton) 0.42 (ton) 216.13 237.31 7/21 13:00:00 82.44 0.01
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 5.4 (kBtu/h) 7.02 (kBtu/h) 133.49 173.75 1/21 09:30:00 -18.94 0.0
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.39 (ton) 0.43 (ton) 224.6 245.79 7/21 13:00:00 82.44 0.01
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 5.35 (kBtu/h) 6.96 (kBtu/h) 133.49 171.63 1/21 09:30:00 -18.94 0.0
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.68 (ton) 0.75 (ton) 385.64 423.78 7/21 16:45:00 80.96 0.01
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 8.01 (kBtu/h) 10.41 (kBtu/h) 194.94 252.15 1/21 09:00:00 -18.94 0.0
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN Cooling 0.32 (ton) 0.35 (ton) 180.1 199.17 7/21 20:00:00 72.95 0.01
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN Heating 5.62 (kBtu/h) 7.31 (kBtu/h) 135.61 177.99 1/21 09:00:00 -18.94 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.31 (ton) 158.92 175.87 7/21 20:00:00 72.95 0.01
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 5.61 (kBtu/h) 7.29 (kBtu/h) 139.85 180.1 1/21 09:30:00 -18.94 0.0
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.3 (ton) 156.8 171.63 7/21 20:00:00 72.95 0.01
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 5.61 (kBtu/h) 7.29 (kBtu/h) 139.85 180.1 1/21 09:30:00 -18.94 0.0
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.55 (ton) 0.6 (ton) 311.48 341.14 7/21 09:00:00 71.89 0.01
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 8.51 (kBtu/h) 11.07 (kBtu/h) 211.89 273.34 1/21 09:30:00 -18.94 0.0
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 336.9 370.8 7/21 17:00:00 80.53 0.01
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 8.46 (kBtu/h) 11.0 (kBtu/h) 209.77 273.34 1/21 09:30:00 -18.94 0.0
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.38 (ton) 0.42 (ton) 216.13 237.31 7/21 13:15:00 82.69 0.01
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 5.61 (kBtu/h) 7.29 (kBtu/h) 139.85 180.1 1/21 09:30:00 -18.94 0.0
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.39 (ton) 0.42 (ton) 218.24 241.55 7/21 13:15:00 82.69 0.01
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 5.61 (kBtu/h) 7.29 (kBtu/h) 139.85 180.1 1/21 09:30:00 -18.94 0.0
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.58 (ton) 0.64 (ton) 328.43 360.21 7/21 09:00:00 71.89 0.01
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 8.51 (kBtu/h) 11.07 (kBtu/h) 211.89 273.34 1/21 09:30:00 -18.94 0.0
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.68 (ton) 0.75 (ton) 387.76 425.89 7/21 16:45:00 80.96 0.01
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 8.46 (kBtu/h) 11.0 (kBtu/h) 209.77 273.34 1/21 09:30:00 -18.94 0.0
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN Cooling 0.86 (ton) 0.95 (ton) 489.46 538.2 7/21 10:00:00 75.47 0.01
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN Heating 8.65 (kBtu/h) 11.24 (kBtu/h) 209.77 273.34 1/21 08:00:00 -18.94 0.0
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN Cooling 0.48 (ton) 0.53 (ton) 271.22 298.76 7/21 15:15:00 83.16 0.01
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN Heating 10.57 (kBtu/h) 13.74 (kBtu/h) 258.5 334.78 1/21 09:00:00 -18.94 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.38 (ton) 0.41 (ton) 214.01 235.2 7/21 14:15:00 83.48 0.01
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 9.16 (kBtu/h) 11.91 (kBtu/h) 222.48 290.29 1/21 09:00:00 -18.94 0.0
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.38 (ton) 0.41 (ton) 214.01 235.2 7/21 14:00:00 83.48 0.01
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 9.16 (kBtu/h) 11.91 (kBtu/h) 222.48 290.29 1/21 09:00:00 -18.94 0.0
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.76 (ton) 0.83 (ton) 428.01 472.51 7/21 09:00:00 71.89 0.01
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 11.87 (kBtu/h) 15.43 (kBtu/h) 290.29 375.04 1/21 09:00:00 -18.94 0.0
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.82 (ton) 0.9 (ton) 464.03 510.65 7/21 16:15:00 81.79 0.01
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 11.81 (kBtu/h) 15.36 (kBtu/h) 288.17 375.04 1/21 09:00:00 -18.94 0.0
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.62 (ton) 0.68 (ton) 349.62 383.52 7/21 13:00:00 82.44 0.01
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 9.16 (kBtu/h) 11.91 (kBtu/h) 222.48 290.29 1/21 09:00:00 -18.94 0.0
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.62 (ton) 0.68 (ton) 351.73 385.64 7/21 12:45:00 82.0 0.01
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 9.16 (kBtu/h) 11.91 (kBtu/h) 222.48 290.29 1/21 09:00:00 -18.94 0.0
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.79 (ton) 0.87 (ton) 449.2 493.7 7/21 09:15:00 72.79 0.01
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 11.87 (kBtu/h) 15.43 (kBtu/h) 290.29 375.04 1/21 09:00:00 -18.94 0.0
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.9 (ton) 0.99 (ton) 508.53 559.38 7/21 15:45:00 82.53 0.01
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 11.81 (kBtu/h) 15.36 (kBtu/h) 288.17 375.04 1/21 09:00:00 -18.94 0.0

Zone Equipment Detail


Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Air Loops Detail


Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:AirLoopHVAC:OutdoorAirSystem Autosized cfm Minimum Outdoor Air Flow Rate 0.00 cfm
OS:Coil:Cooling:DX:SingleSpeed Autosized Btu/h Rated COP 3.44 COP
OS:Coil:Heating:Electric Autosized Btu/h Efficiency 1.00
OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O
OS:SetpointManager:Scheduled Control Variable - Temperature 68.0 to 68.0 F
(demand)
Thermal Zones Total Floor Area 82,565 ft^2 88
Thermal Zones thermostat ranges for cooling 75.2 to 75.2 F
Thermal Zones thermostat ranges for heating 64.4 to 71.6 F
Terminal Types Used OS:AirTerminal:SingleDuct:Uncontrolled 88
(controls)
HVAC Operation Schedule Make-up air unit Occ Sch
Night Cycle Setting CycleOnAny Choice
Economizer Setting DifferentialEnthalpy Choice
Demand Controlled Ventilation Status false Bool

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:AirLoopHVAC:OutdoorAirSystem Autosized cfm Minimum Outdoor Air Flow Rate 0.00 cfm
OS:Coil:Cooling:Water Autosized gal/min Plant Loop Chilled Water Loop
OS:Coil:Heating:Electric Autosized Btu/h Efficiency 1.00
OS:Fan:VariableVolume Autosized cfm Pressure Rise 5.85 inH_{2}O
OS:SetpointManager:Scheduled Control Variable - Temperature 55.4 to 55.4 F
(demand)
Thermal Zones Total Floor Area 1,786 ft^2 2
Thermal Zones thermostat ranges for cooling 75.2 to 95.0 F
Thermal Zones thermostat ranges for heating 64.4 to 71.6 F
Terminal Types Used OS:AirTerminal:SingleDuct:VAV:Reheat 2
(controls)
HVAC Operation Schedule VAV with Reheat Occ Sch
Night Cycle Setting CycleOnAny Choice
Economizer Setting NoEconomizer Choice
Demand Controlled Ventilation Status false Bool

Plant Loops Detail


Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:Chiller:Electric:EIR 21,898.42 Btu/h Reference COP 4.50
OS:Chiller:Electric:EIR (cont) Chiller Source Condenser Water Loop
OS:SetpointManager:Scheduled Control Variable - Temperature 44.6 to 44.6 F
OS:Chiller:Electric:EIR 0.00 Btu/h Reference COP 4.50
OS:Chiller:Electric:EIR (cont) Chiller Source Condenser Water Loop
(demand)
OS:Coil:Cooling:Water Air Loop VAV with Reheat
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 32.0 to 212.0 F
Design Loop Exit Temperature 44.60 F
Loop Design Temperature Difference 10.80 R

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:CoolingTower:SingleSpeed - Air Autosized gal/min
OS:CoolingTower:SingleSpeed (cont) - Water Autosized cfm Fan Power at Design Air Flow Rate 249,274.24 W
OS:SetpointManager:Scheduled Control Variable - Temperature 84.2 to 84.2 F
(demand)
OS:Chiller:Electric:EIR Plant Loop Chilled Water Loop
OS:Chiller:Electric:EIR Plant Loop Chilled Water Loop
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 32.0 to 212.0 F
Design Loop Exit Temperature 84.20 F
Loop Design Temperature Difference 10.80 R

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:WaterHeater:Mixed 600 gal Heater Thermal Efficiency 1.00 fraction
OS:SetpointManager:Scheduled Control Variable - Temperature 140.0 to 140.0 F
(demand)
OS:WaterUse:Connections Water Use Connections 1
OS:WaterUse:Connections Water Use Connections 2
OS:WaterUse:Connections Water Use Connections 3
OS:WaterUse:Connections Water Use Connections 4
OS:WaterUse:Connections Water Use Connections 5
OS:WaterUse:Connections Water Use Connections 6
OS:WaterUse:Connections Water Use Connections 7
OS:WaterUse:Connections Water Use Connections 8
OS:WaterUse:Connections Water Use Connections 9
OS:WaterUse:Connections Water Use Connections 10
OS:WaterUse:Connections Water Use Connections 11
OS:WaterUse:Connections Water Use Connections 12
OS:WaterUse:Connections Water Use Connections 13
OS:WaterUse:Connections Water Use Connections 14
OS:WaterUse:Connections Water Use Connections 15
OS:WaterUse:Connections Water Use Connections 16
OS:WaterUse:Connections Water Use Connections 17
OS:WaterUse:Connections Water Use Connections 18
OS:WaterUse:Connections Water Use Connections 19
OS:WaterUse:Connections Water Use Connections 20
OS:WaterUse:Connections Water Use Connections 21
OS:WaterUse:Connections Water Use Connections 22
OS:WaterUse:Connections Water Use Connections 23
OS:WaterUse:Connections Water Use Connections 24
OS:WaterUse:Connections Water Use Connections 25
OS:WaterUse:Connections Water Use Connections 26
OS:WaterUse:Connections Water Use Connections 27
OS:WaterUse:Connections Water Use Connections 28
OS:WaterUse:Connections Water Use Connections 29
OS:WaterUse:Connections Water Use Connections 30
OS:WaterUse:Connections Water Use Connections 31
OS:WaterUse:Connections Water Use Connections 32
OS:WaterUse:Connections Water Use Connections 33
OS:WaterUse:Connections Water Use Connections 34
OS:WaterUse:Connections Water Use Connections 35
OS:WaterUse:Connections Water Use Connections 36
OS:WaterUse:Connections Water Use Connections 37
OS:WaterUse:Connections Water Use Connections 38
OS:WaterUse:Connections Water Use Connections 39
OS:WaterUse:Connections Water Use Connections 40
OS:WaterUse:Connections Water Use Connections 41
OS:WaterUse:Connections Water Use Connections 42
OS:WaterUse:Connections Water Use Connections 43
OS:WaterUse:Connections Water Use Connections 44
OS:WaterUse:Connections Water Use Connections 45
OS:WaterUse:Connections Water Use Connections 46
OS:WaterUse:Connections Water Use Connections 47
OS:WaterUse:Connections Water Use Connections 48
OS:WaterUse:Connections Water Use Connections 49
OS:WaterUse:Connections Water Use Connections 50
OS:WaterUse:Connections Water Use Connections 51
OS:WaterUse:Connections Water Use Connections 52
OS:WaterUse:Connections Water Use Connections 53
OS:WaterUse:Connections Water Use Connections 54
OS:WaterUse:Connections Water Use Connections 55
OS:WaterUse:Connections Water Use Connections 56
OS:WaterUse:Connections Water Use Connections 57
OS:WaterUse:Connections Water Use Connections 58
OS:WaterUse:Connections Water Use Connections 59
OS:WaterUse:Connections Water Use Connections 60
OS:WaterUse:Connections Water Use Connections 61
OS:WaterUse:Connections Water Use Connections 62
OS:WaterUse:Connections Water Use Connections 63
OS:WaterUse:Connections Water Use Connections 64
OS:WaterUse:Connections Water Use Connections 65
OS:WaterUse:Connections Water Use Connections 66
OS:WaterUse:Connections Water Use Connections 67
OS:WaterUse:Connections Water Use Connections 68
OS:WaterUse:Connections Water Use Connections 69
OS:WaterUse:Connections Water Use Connections 70
OS:WaterUse:Connections Water Use Connections 71
OS:WaterUse:Connections Water Use Connections 72
OS:WaterUse:Connections Water Use Connections 73
OS:WaterUse:Connections Water Use Connections 74
OS:WaterUse:Connections Water Use Connections 75
OS:WaterUse:Connections Water Use Connections 76
OS:WaterUse:Connections Water Use Connections 77
OS:WaterUse:Connections Water Use Connections 78
OS:WaterUse:Connections Water Use Connections 79
OS:WaterUse:Connections Water Use Connections 80
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 50.0 to 140.0 F
Design Loop Exit Temperature 140.00 F
Loop Design Temperature Difference 9.00 R

Outdoor Air


Average Number of Occupants Nominal Number of Occupants Zone Volume (ft^3) Avg. Mechanical Ventilation (ach) Min. Mechanical Ventilation (ach) Avg. Infiltration (ach) Min. Infiltration (ach) Avg. Simple Ventilation (ach) Min. Simple Ventilation (ach)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.424 0.35 0.009 0.0 0.0 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.467 0.394 0.029 0.0 0.0 0.0
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.467 0.394 0.029 0.0 0.0 0.0
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.461 0.393 0.048 0.0 0.0 0.0
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.457 0.393 0.048 0.0 0.0 0.0
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.489 0.396 0.029 0.0 0.0 0.0
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.489 0.396 0.029 0.0 0.0 0.0
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.483 0.394 0.048 0.0 0.0 0.0
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.472 0.395 0.048 0.0 0.0 0.0
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.426 0.35 0.011 0.0 0.0 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.471 0.394 0.034 0.0 0.0 0.0
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.471 0.394 0.034 0.0 0.0 0.0
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.462 0.393 0.056 0.0 0.0 0.0
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.458 0.393 0.056 0.0 0.0 0.0
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.492 0.397 0.034 0.0 0.0 0.0
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.491 0.397 0.034 0.0 0.0 0.0
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.484 0.395 0.056 0.0 0.0 0.0
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.474 0.395 0.056 0.0 0.0 0.0
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.427 0.35 0.012 0.0 0.0 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.471 0.394 0.038 0.0 0.0 0.0
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.47 0.394 0.038 0.0 0.0 0.0
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.462 0.393 0.063 0.0 0.0 0.0
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.458 0.393 0.063 0.0 0.0 0.0
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.492 0.397 0.038 0.0 0.0 0.0
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.491 0.397 0.038 0.0 0.0 0.0
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.484 0.395 0.063 0.0 0.0 0.0
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.474 0.395 0.063 0.0 0.0 0.0
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.426 0.35 0.015 0.0 0.0 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.469 0.394 0.044 0.0 0.0 0.0
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.469 0.394 0.044 0.0 0.0 0.0
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.462 0.393 0.073 0.0 0.0 0.0
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.458 0.393 0.073 0.0 0.0 0.0
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.49 0.397 0.044 0.0 0.0 0.0
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.49 0.397 0.044 0.0 0.0 0.0
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.483 0.395 0.073 0.0 0.0 0.0
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.473 0.395 0.073 0.0 0.0 0.0
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.426 0.35 0.015 0.0 0.0 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.468 0.394 0.047 0.0 0.0 0.0
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.468 0.394 0.047 0.0 0.0 0.0
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.461 0.393 0.077 0.0 0.0 0.0
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.457 0.393 0.077 0.0 0.0 0.0
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.489 0.397 0.047 0.0 0.0 0.0
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.489 0.397 0.047 0.0 0.0 0.0
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.483 0.395 0.077 0.0 0.0 0.0
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.472 0.395 0.077 0.0 0.0 0.0
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.424 0.35 0.016 0.0 0.0 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.466 0.394 0.049 0.0 0.0 0.0
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.466 0.394 0.049 0.0 0.0 0.0
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.461 0.393 0.081 0.0 0.0 0.0
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.457 0.393 0.081 0.0 0.0 0.0
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.487 0.396 0.049 0.0 0.0 0.0
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.487 0.396 0.049 0.0 0.0 0.0
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.481 0.394 0.081 0.0 0.0 0.0
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.471 0.394 0.081 0.0 0.0 0.0
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.416 0.349 0.017 0.0 0.0 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.459 0.394 0.051 0.0 0.0 0.0
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.459 0.394 0.051 0.0 0.0 0.0
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.459 0.393 0.084 0.0 0.0 0.0
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.454 0.393 0.084 0.0 0.0 0.0
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.481 0.396 0.051 0.0 0.0 0.0
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.481 0.396 0.051 0.0 0.0 0.0
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.478 0.394 0.084 0.0 0.0 0.0
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.467 0.394 0.084 0.0 0.0 0.0
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.128 0.0 0.007 0.0 0.0 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.454 0.394 0.02 0.0 0.0 0.0
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.454 0.394 0.02 0.0 0.0 0.0
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.451 0.393 0.033 0.0 0.0 0.0
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.449 0.393 0.033 0.0 0.0 0.0
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.476 0.396 0.02 0.0 0.0 0.0
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.476 0.396 0.02 0.0 0.0 0.0
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.466 0.394 0.033 0.0 0.0 0.0
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.427 0.35 0.014 0.0 0.0 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.47 0.394 0.041 0.0 0.0 0.0
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.47 0.394 0.041 0.0 0.0 0.0
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.462 0.393 0.068 0.0 0.0 0.0
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.458 0.393 0.068 0.0 0.0 0.0
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.491 0.397 0.041 0.0 0.0 0.0
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.491 0.397 0.041 0.0 0.0 0.0
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.484 0.395 0.068 0.0 0.0 0.0
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.473 0.395 0.068 0.0 0.0 0.0
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 2.37 4.42 9498 0.605 0.332 0.037 0.0 0.0 0.0
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.397 0.347 0.149 0.0 0.0 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.445 0.393 0.184 0.0 0.0 0.0
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.445 0.393 0.184 0.0 0.0 0.0
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.448 0.393 0.219 0.0 0.0 0.0
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.446 0.393 0.219 0.0 0.0 0.0
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.46 0.393 0.184 0.0 0.0 0.0
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.46 0.393 0.184 0.0 0.0 0.0
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.463 0.393 0.219 0.0 0.0 0.0
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.458 0.393 0.219 0.0 0.0 0.0

Cash Flow

No Data to Show for Cash Flow

Site and Source Summary


Total Energy (kBtu) Energy Per Total Building Area (kBtu/ft^2) Energy Per Conditioned Building Area (kBtu/ft^2)
Total Site Energy 3587317.3 42.5 42.5
Net Site Energy 3587317.3 42.5 42.5
Total Source Energy 11361038.6 134.7 134.7
Net Source Energy 11361038.6 134.7 134.7

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613

Schedule Overview


Schedule Type Limits Rules Use Count
Air Velocity Schedule Velocity 0 3
Always On Dimensionless 0 90
CHW Temp Temperature 3 1
Clothing Schedule ClothingInsulation 1 3
CW Temp Temperature 3 1
Make-up air unit Occ Sch Dimensionless 7 2
Makeup-Air Unit Supply Air Temp Temperature 0 1
NECB-A-Electric-Equipment Dimensionless 3 1
NECB-A-Lighting Dimensionless 3 1
NECB-A-Occupancy Dimensionless 3 1
NECB-A-Service Water Heating Dimensionless 3 1
NECB-A-Thermostat Setpoint-Cooling Temperature 3 3
NECB-A-Thermostat Setpoint-Heating Temperature 3 3
NECB-Activity ActivityLevel 0 90
NECB-G-Electric-Equipment Dimensionless 3 89
NECB-G-Lighting Dimensionless 3 89
NECB-G-Occupancy Dimensionless 3 89
NECB-G-Service Water Heating Dimensionless 3 79
NECB-G-Thermostat Setpoint-Cooling Temperature 3 180
NECB-G-Thermostat Setpoint-Heating Temperature 3 180
ON_OFF_ALWAYS_OFF Availability 3 88
Schedule Ruleset 10 0 1
Schedule Ruleset 100 0 1
Schedule Ruleset 101 0 1
Schedule Ruleset 102 0 1
Schedule Ruleset 103 0 1
Schedule Ruleset 104 0 1
Schedule Ruleset 105 0 1
Schedule Ruleset 106 0 1
Schedule Ruleset 107 0 1
Schedule Ruleset 108 0 1
Schedule Ruleset 109 0 1
Schedule Ruleset 11 0 1
Schedule Ruleset 110 0 1
Schedule Ruleset 111 0 1
Schedule Ruleset 112 0 1
Schedule Ruleset 113 0 1
Schedule Ruleset 114 0 1
Schedule Ruleset 115 0 1
Schedule Ruleset 116 0 1
Schedule Ruleset 117 0 1
Schedule Ruleset 118 0 1
Schedule Ruleset 119 0 1
Schedule Ruleset 12 0 1
Schedule Ruleset 120 0 1
Schedule Ruleset 121 0 1
Schedule Ruleset 122 0 1
Schedule Ruleset 123 0 1
Schedule Ruleset 124 0 1
Schedule Ruleset 125 0 1
Schedule Ruleset 126 0 1
Schedule Ruleset 127 0 1
Schedule Ruleset 128 0 1
Schedule Ruleset 129 0 1
Schedule Ruleset 13 0 1
Schedule Ruleset 130 0 1
Schedule Ruleset 131 0 1
Schedule Ruleset 132 0 1
Schedule Ruleset 133 0 1
Schedule Ruleset 134 0 1
Schedule Ruleset 135 0 1
Schedule Ruleset 136 0 1
Schedule Ruleset 137 0 1
Schedule Ruleset 138 0 1
Schedule Ruleset 139 0 1
Schedule Ruleset 14 0 1
Schedule Ruleset 140 0 1
Schedule Ruleset 141 0 1
Schedule Ruleset 142 0 1
Schedule Ruleset 143 0 1
Schedule Ruleset 144 0 1
Schedule Ruleset 145 0 1
Schedule Ruleset 146 0 1
Schedule Ruleset 147 0 1
Schedule Ruleset 148 0 1
Schedule Ruleset 149 0 1
Schedule Ruleset 15 0 1
Schedule Ruleset 150 0 1
Schedule Ruleset 151 0 1
Schedule Ruleset 152 0 1
Schedule Ruleset 153 0 1
Schedule Ruleset 154 0 1
Schedule Ruleset 155 0 1
Schedule Ruleset 156 0 1
Schedule Ruleset 157 0 1
Schedule Ruleset 158 0 1
Schedule Ruleset 159 0 1
Schedule Ruleset 16 0 1
Schedule Ruleset 160 0 1
Schedule Ruleset 161 0 1
Schedule Ruleset 162 0 1
Schedule Ruleset 163 0 1
Schedule Ruleset 164 0 1
Schedule Ruleset 165 0 1
Schedule Ruleset 166 0 1
Schedule Ruleset 167 0 1
Schedule Ruleset 168 0 1
Schedule Ruleset 169 0 1
Schedule Ruleset 17 0 1
Schedule Ruleset 170 0 1
Schedule Ruleset 171 0 1
Schedule Ruleset 172 0 1
Schedule Ruleset 173 0 1
Schedule Ruleset 174 0 1
Schedule Ruleset 175 0 1
Schedule Ruleset 176 0 1
Schedule Ruleset 177 0 1
Schedule Ruleset 178 0 1
Schedule Ruleset 179 0 1
Schedule Ruleset 18 0 1
Schedule Ruleset 180 0 1
Schedule Ruleset 181 0 1
Schedule Ruleset 182 0 1
Schedule Ruleset 183 0 1
Schedule Ruleset 184 0 1
Schedule Ruleset 185 0 1
Schedule Ruleset 186 0 1
Schedule Ruleset 187 0 1
Schedule Ruleset 188 0 1
Schedule Ruleset 189 0 1
Schedule Ruleset 19 0 1
Schedule Ruleset 190 0 1
Schedule Ruleset 191 0 1
Schedule Ruleset 192 0 1
Schedule Ruleset 193 0 1
Schedule Ruleset 194 0 1
Schedule Ruleset 195 0 1
Schedule Ruleset 196 0 1
Schedule Ruleset 197 0 1
Schedule Ruleset 198 0 1
Schedule Ruleset 199 0 1
Schedule Ruleset 20 0 1
Schedule Ruleset 200 0 1
Schedule Ruleset 201 0 1
Schedule Ruleset 202 0 1
Schedule Ruleset 203 0 1
Schedule Ruleset 204 0 1
Schedule Ruleset 205 0 1
Schedule Ruleset 206 0 1
Schedule Ruleset 207 0 1
Schedule Ruleset 208 0 1
Schedule Ruleset 209 0 1
Schedule Ruleset 21 0 1
Schedule Ruleset 210 0 1
Schedule Ruleset 211 0 1
Schedule Ruleset 212 0 1
Schedule Ruleset 213 0 1
Schedule Ruleset 214 0 1
Schedule Ruleset 215 0 1
Schedule Ruleset 216 0 1
Schedule Ruleset 217 0 1
Schedule Ruleset 218 0 1
Schedule Ruleset 219 0 1
Schedule Ruleset 22 0 1
Schedule Ruleset 220 0 1
Schedule Ruleset 221 0 1
Schedule Ruleset 222 0 1
Schedule Ruleset 223 0 1
Schedule Ruleset 224 0 1
Schedule Ruleset 225 0 1
Schedule Ruleset 226 0 1
Schedule Ruleset 227 0 1
Schedule Ruleset 228 0 1
Schedule Ruleset 229 0 1
Schedule Ruleset 23 0 1
Schedule Ruleset 230 0 1
Schedule Ruleset 231 0 1
Schedule Ruleset 232 0 1
Schedule Ruleset 233 0 1
Schedule Ruleset 234 0 1
Schedule Ruleset 235 0 1
Schedule Ruleset 236 0 1
Schedule Ruleset 237 0 1
Schedule Ruleset 238 0 1
Schedule Ruleset 239 0 1
Schedule Ruleset 24 0 1
Schedule Ruleset 240 0 1
Schedule Ruleset 241 0 1
Schedule Ruleset 242 0 1
Schedule Ruleset 25 0 1
Schedule Ruleset 26 0 1
Schedule Ruleset 27 0 1
Schedule Ruleset 28 0 1
Schedule Ruleset 29 0 1
Schedule Ruleset 3 0 1
Schedule Ruleset 30 0 1
Schedule Ruleset 31 0 1
Schedule Ruleset 32 0 1
Schedule Ruleset 33 0 1
Schedule Ruleset 34 0 1
Schedule Ruleset 35 0 1
Schedule Ruleset 36 0 1
Schedule Ruleset 37 0 1
Schedule Ruleset 38 0 1
Schedule Ruleset 39 0 1
Schedule Ruleset 4 0 1
Schedule Ruleset 40 0 1
Schedule Ruleset 41 0 1
Schedule Ruleset 42 0 1
Schedule Ruleset 43 0 1
Schedule Ruleset 44 0 1
Schedule Ruleset 45 0 1
Schedule Ruleset 46 0 1
Schedule Ruleset 47 0 1
Schedule Ruleset 48 0 1
Schedule Ruleset 49 0 1
Schedule Ruleset 5 0 1
Schedule Ruleset 50 0 1
Schedule Ruleset 51 0 1
Schedule Ruleset 52 0 1
Schedule Ruleset 53 0 1
Schedule Ruleset 54 0 1
Schedule Ruleset 55 0 1
Schedule Ruleset 56 0 1
Schedule Ruleset 57 0 1
Schedule Ruleset 58 0 1
Schedule Ruleset 59 0 1
Schedule Ruleset 6 0 1
Schedule Ruleset 60 0 1
Schedule Ruleset 61 0 1
Schedule Ruleset 62 0 1
Schedule Ruleset 63 0 1
Schedule Ruleset 64 0 1
Schedule Ruleset 65 0 1
Schedule Ruleset 66 0 1
Schedule Ruleset 67 0 1
Schedule Ruleset 68 0 1
Schedule Ruleset 69 0 1
Schedule Ruleset 7 0 1
Schedule Ruleset 70 0 1
Schedule Ruleset 71 0 1
Schedule Ruleset 72 0 1
Schedule Ruleset 73 0 1
Schedule Ruleset 74 0 1
Schedule Ruleset 75 0 1
Schedule Ruleset 76 0 1
Schedule Ruleset 77 0 1
Schedule Ruleset 78 0 1
Schedule Ruleset 79 0 1
Schedule Ruleset 8 0 1
Schedule Ruleset 80 0 1
Schedule Ruleset 81 0 1
Schedule Ruleset 82 0 1
Schedule Ruleset 83 0 1
Schedule Ruleset 84 0 1
Schedule Ruleset 85 0 1
Schedule Ruleset 86 0 1
Schedule Ruleset 87 0 1
Schedule Ruleset 88 0 1
Schedule Ruleset 89 0 1
Schedule Ruleset 9 0 1
Schedule Ruleset 90 0 1
Schedule Ruleset 91 0 1
Schedule Ruleset 92 0 1
Schedule Ruleset 93 0 1
Schedule Ruleset 94 0 1
Schedule Ruleset 95 0 1
Schedule Ruleset 96 0 1
Schedule Ruleset 97 0 1
Schedule Ruleset 98 0 1
Schedule Ruleset 99 0 1
Service Water Loop Temp - 140F Temperature 0 2
Supply Air Temp Temperature 0 1
VAV with Reheat Occ Sch Dimensionless 7 2
Water Heater Ambient Temp Schedule - 70F Temperature 0 1
Work Efficiency Schedule Dimensionless 0 3